Arc flash assessment, hazard study and short circuit fault current calculation  
  Frequently Asked Questions
  Expert Advice for
Arc Flash Analysis
 
   Home
 
  SHORT CIRCUITS:
   Calculator
   Reference Data
 
  ARC FLASH:
AFA v3.0
   NFPA 70E Calc
   IEEE 1584 Calc
   Tool Overview
 
  Transfer Switches
 
   Info / FAQ
   Examples
 
  Blog
   Contact Us
   Testimonials
   Terms of Use
   News & Links
   Site Map

national-safety.net
advertise with us

Advertise
with ArcAd

Steps of performing short circuit analysis. Up to the Questions

1. 

Create an account if you don't already have one, and log onto the page where you can add components one by one to build up a radial electrical distribution system. The components can be a power source, transformers, bus ducts, cables, motors and generators, or "special" components whereby the user can define his own X and R values for a non-standard device.

2. Build a one line diagram of distribution system [example].
3.

Pre-assign each basic component within the industrial electrical distribution system a single short circuit MVA factor (SC MVA) based on the impedance it adds to the system, and X/R ratio [more...].

4.

Perform transformation of delta connected components of power distribution system to wye connection before the MVA method implemented in the calculator can be apppied [more...].

5.

Develop a hierarchical tree in terms of database records [more...] Loads not contributing to system's short circuit current (lighting, heating) are assigned a SC MVA value of 0. Unloaded transformers should also be terminated with the SC MVA = 0 node - this allows to calculate short circuits on the unloaded transformer secondary.

6.

Now, as you have all the required data on hand, login and programm in your power distribution system. When finished, click Display button to calculate symmetrical 3 phase bolted fault short circuit MVA from the data compiled in steps 1 to 3. Divide total SC MVA values by 1.73 * kVLL to get short circuit values in kA, or use accompanying SCMVA to KA converter to do it for you:

SC MVA to SC KA Converter
SCMVA: Voltage, kV: KA
By performing short circuit MVA analysis for positive, negative and zero sequences, unsymmetrical fault (Phase to ground, Phase to phase) currents can be resolved (see how):

Arc Flash Study &
Labels per NFPA 70E

Electric arc flash calculator

AFA V3.0 , V2.0

Arc Flash Label
Printing Services

Label Printing Services
Generator Transfer Switch

Generator
Transfer Switches

Write us at: