Arc flash assessment, hazard study and short circuit fault current calculation  
  Frequently Asked Questions
 

Click Here for
Your Service Guide

 
   Home
 
  SHORT CIRCUITS:
   Calculator
   Reference Data
 
  ARC FLASH:
   IEEE 1584
   Procedure
 
   Info / FAQ
   Examples
 
    Blog
   Test Zone
   Contact Us
   Testimonials
   Terms of Use
   News & Links
   Site Map




SC MVA to short circuit current kA conversion Up to the Questions

The program outputs the hierarchical system equipment tree with short circuit MVA calculated at each node. Short circuits contributed by upstream (red) and downstream (blue) equipment are listed across each node ( see sample output ). For a three phase fault, use the accompanying SC MVA to KA converter (see below) or simply divide total SC MVA value by 1.73 * kVLL to get short circuit current values in kA.

SC MVA to SC KA Converter
SCMVA: Voltage, kV: KA
Three phase faults are unique in that they are balanced ( symmetrical) in the three phases, and can be calculated from the single one line diagram.The resulting short circuit current values in kA are suitable for arcflash calculations, or any other study requiring symmetrical three phase bolted fault current analysis.
The protection specialist is interested in a wider variety of faults than just three phase fault. The most common fault is a single phase to earth fault which in low voltage systems can produce a higher fault current than a three phase fault. Experience has shown that between 70 to 80 percent of transmission line faults are single line to ground faults, which arise from the flashover of only one line to the tower and ground. Similarly, because protection is expected to operate correctly for all types of fault, it may be necessary to consider the fault currents due to many different types of fault. Since the three-phase fault is unique in being a balanced fault, a method of analysis that is applicable to unbalanced faults is required. It can be shown that, by applying the principle of superposition, any general three-phase system of vectors may be replaced by three sets of balanced (symmetrical) vectors; two sets are three-phase but having opposite phase rotation and one set is co-phasal. These vector sets are described as the positive, negative and zero sequence sets respectively. By performing short circuit MVA analysis for all the three sequences, unsymmetrical fault currents can be resolved by substituting respective SC MVA (1, 2 and 0) and X/R into the form below. When filled in, the form will calculate 3 phase, phase to ground and phase to phase faults. Impedance Ohmic value and x/r are required for faults through impedance. VLL, SC MVA and X/R should be numerical above 0. Leave SC MVA2, 0, X/R2, 0 blank if unbalanced fault currents are of no interest.

   
VLL
kV
MVA1
SC MVA
XR1
X/R
MVA2
SC MVA
XR2
X/R
MVA0
SC MVA
XR0
X/R
ZF
Ohm
XRZF
X/R
 

Write us at: